供应张力控制器 PFEA112-65 3BSE030369R0065 ARCSARC3-arc_flt_det ARCSARC1运行ARCSARC2运行ARCSARC3运行DARREC1 inpro DARREC2-close_cb DARREC1-UNSC_recl TCSCBR2闭塞报警 BI 1(阻塞) BI 2(断路器关闭) BI 3(断路器开路) TRPPTRC1-跳闸或 TRPPTRC2-跳闸 TCSCBR1阻塞报警或LED9(TCS报警) 干扰记录器 A071324 V6 EN 图26:干扰记录器 来自保护级的所有启动和运行信号都被路由以触发 干扰记录器,或仅由干扰记录 记录器取决于参数设置。此外,选择 自动重合闸、电弧保护信号和X120的三个二进制输入为 也连接。 包括两个独立的跳闸电路监控功能,用于PO3的TCSCBR1 (X100:15-19)和用于PO4的TCSCBr2(X100:20-24)。两个功能都被阻止 通过主跳闸(TRPPTRC1和TRPPTRC2)和断路器断开 信号TCS报警指示连接至LED 9。 第3节1MRS756378 K REF615标准配置 62参考文献615 应用手册 默认情况下,预期中没有外部电阻器 断路器跳闸线圈电路与电路并联 断路器常开辅助触点。 3.5.3.3控制和联锁功能图 PHLPTOC1运行PHHPTOC1运行PHHPTOC2运行PHIPTOC1运行NSPTOC1运行NSPTOC运行 PDNSPTOC1操作DEFLPDEF1操作EFHPTOC1跳闸线圈1 PO3 TRPPTRC1块操作RST_LKOUT 带锁定模式选择的跳闸CL_LKOUT TRPPTRC2块操作RST_LKOUT 带锁定模式选择的跳闸CL_LKOUT DARREC1开路断路器 CBXCBR1-exe_op 主跳闸#2 DEFLPDEF2操作DEFHPDEF1操作EFPADM1操作EFPADM2操作EFPADM3操作INTRPTEF1操作ROVPTOV1操作ROVPTOV3操作ROVPTOV2操作ARCSARC1操作ARCSARC2操作ARCSARC3操作 PHLPTOC1运行PHHPTOC1运行PHHPTOC2运行PHIPTOC1运行NSPTOC1运行NSPTOC运行 PDNSPTOC1操作DEFLPDEF1操作EFHPTOC1操作或 DEFLPDEF2操作DEFHPDEF1操作EFPADM1操作EFPADM2操作EFPADM3操作INTRPTEF1操作ROVPTOV1操作ROVPTOV3操作ROVPTOV2操作ARCSARC1操作ARCSARC2操作ARCSARC3操作CCBRBRF1 trret WPWDE1操作WPWDE2操作WPWDE3操作 WPWDE1操作WPWDE2操作WPWDE3操作 开路断路器/ 跳闸线圈2 A071326 V6 EN 图27:主跳闸 来自保护装置的操作信号连接至双跳闸输出 通过相应的主设备联系PO3(X100:15-19)和PO4(X100:20-24) 跳闸TRPPTRC1和TRPPTRC2。断路器的断开控制命令 从本地或远程CBXCBR1-exe_op或自动重合闸器DARREC1- open_ cb直接连接到输出PO3(X100:15-19)。 TRPPTRC1和2提供锁定/闭锁功能、事件生成和 跳闸信号持续时间设置。如果选择了锁定操作模式,一个二进制有两种类型的隔离开关和接地开关块可用。 DCSXSWI1…3和ESSSWI1…2仅为状态类型,而DCXSWI1…2和 ESXSWI1为可控型。默认情况下,仅连接状态块 标准配置逻辑。如果选可控操作,则可控 可以使用隔离开关和接地开关块的类型,而不是状态 这是的类型。可以完成控制块的连接和配置 使用PCM600。 附加卡X110的二进制输入5和6用于母线 隔离开关(DCSXSWI1)或断路器支架位置指示。 表20:二进制输入5和6表示的设备位置 待通电的一次设备位置输入 输入5(X110:8-9)输入6(X110:10-9) 母线隔离开关闭合x 母线隔离开关断开x 断路器台车处于工作位置x 断路器台车处于测试位置x 第3节1MRS756378 K REF615标准配置 64参考文献615 应用手册 二进制输入7和8(X110:11-13)用于以下位置指示: 线路侧接地开关。 当ENA_CLOSE输入激活时,断路器闭合被启用。 输入可由配置逻辑激活,配置逻辑是 隔离开关或断路器支架和接地开关位置状态以及状态 主跳闸逻辑、气压报警和断路器弹簧充电。 DCSXSWI的OKPOS输出定义了隔离开关或断路器卡车是否: 打开(测试位置)或关闭(维修位置)。这个,一起 在接地开关断开和非激活跳闸信号的情况下,激活闭合启用 向断路器控制功能块发送信号。开放操作始终是 启用。自动重合闸关闭命令信号直接连接到 输出触点PO1(X100:6-7)。 例如,ITL_BYPASS输入可用于始终启用关闭 当断路器支架处于试验位置时,断路器 当断路器 供应张力控制器 PFEA112-65 3BSE030369R0065 供应张力控制器 PFEA112-65 3BSE030369R0065 供应张力控制器 PFEA112-65 3BSE030369R0065 ARCSARC3-arc_flt_det ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate DARREC1-inpro DARREC1-close_cb DARREC1-unsuc_recl TCSSCBR2 BLOCK ALARM BI 1 (Blocking) BI 2 (CB Closed) BI 3 (CB Open) TRPPTRC1 - trip OR TRPPTRC2 - trip TCSSCBR1 BLOCK ALARM OR LED9 (TCS ALARM) DISTURBANCE RECORDER A071324 V6 EN Figure 26: Disturbance recorder All start and operate signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings. Additionally, the selected autorecloser, the ARC protection signals and the three binary inputs from X120 are also connected. Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indication is connected to LED 9. Section 3 1MRS756378 K REF615 standard configurations 62 REF615 Application Manual By default it is expected that there is no external resistor in the circuit breaker tripping coil circuit connected parallel with circuit breaker normally open auxiliary contact. 3.5.3.3 Functional diagrams for control and interlocking PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate PDNSPTOC1-operate DEFLPDEF1-operate EFHPTOC1-trip coil 1 PO3 TRPPTRC1 BLOCK OPERATE RST_LKOUT TRIP CL_LKOUT With lock-out mode selection TRPPTRC2 BLOCK OPERATE RST_LKOUT TRIP CL_LKOUT With lock-out mode selection DARREC1-open cb CBXCBR1-exe_op MASTER TRIP #2 DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate ROVPTOV1-operate ROVPTOV3-operate ROVPTOV2-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate PDNSPTOC1-operate DEFLPDEF1-operate EFHPTOC1-operate OR DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate ROVPTOV1-operate ROVPTOV3-operate ROVPTOV2-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate CCBRBRF1-trret WPWDE1-operate WPWDE2-operate WPWDE3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate Open CB / trip coil 2 A071326 V6 EN Figure 27: Master trip The operate signals from the protections are connected to the two trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1- open_cb are connected directly to the output PO3 (X100:15-19). TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip signal duration setting. If the lockout operation mode is selected, one binaryThere are two types of disconnector and earthing switch blocks available. DCSXSWI1...3 and ESSXSWI1...2 are status only type, and DCXSWI1...2 and ESXSWI1 are controllable type. By default, the status only blocks are connected in standard configuration logic. If controllable operation is preferred, the controllable type of disconnector and earthing switch blocks can be used instead of the status only type. The connection and configuration of the control blocks can be done using PCM600. The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DCSXSWI1) or circuit-breaker truck position indication. Table 20: Device positions indicated by binary inputs 5 and 6 Primary device position Input to be energized Input 5 (X110:8-9) Input 6 (X110:10-9) Busbar disconnector closed x Busbar disconnector open x Circuit breaker truck in service position x Circuit breaker truck in test position x Section 3 1MRS756378 K REF615 standard configurations 64 REF615 Application Manual The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line-side earth switch. The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input can be activated by the configuration logic, which is a combination of the disconnector or breaker truck and earth-switch position statuses and the statuses of the master trip logics and gas pressure alarm and circuit-breaker spring charging. The OKPOS output from DCSXSWI defines if the disconnector or breaker truck is definitely either open (in test position) or close (in service position). This, together with the open earth-switch and non-active trip signals, activates the close-enable signal to the circuit breaker control function block. The open operation is always enabled. The auto-recloser close command signals are directly connected to the output contact PO1 (X100:6-7). The ITL_BYPASS input can be used, for example, to always enable the closing of the circuit breaker when the circuit breaker truck is in the test position, despite of the interlocking conditions being active when the circuit breaker truck is closed in service position. If the ENA_CLOSE signal is completely removed from the breaker control function block CBXCBR with PCM600, the function assumes that the breaker close commands are allowed continuously. The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker status based on the binary input information connected and measured current levels. The function introduces various supervision methods. The corresponding supervision alarm signals are routed to LED 1MRS756378 K Section 3 REF615 standard configurations REF615 65 Application Manual COMMON ALARM / INDICATION 1 & 2 Start Indication Operate Indication SO1 SO2 PHLPTOC1-start PHHPTOC1-start PHHPTOC2-start PHIPTOC1-start NSPTOC1-start NSPTOC2-start PDNSPTOC1-start DEFLPDEF1-start EFHPTOC1-start OR DEFLPDEF2-start DEFHPDEF1-start EFPADM1-start EFPADM2-start EFPADM3-start INTRPTEF1-start ROVPTOV1-start ROVPTOV3-start ROVPTOV2-start WPWDE1-start WPWDE2-start WPWDE3-start PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate NSPTOC1-operate NSPTOC2-operate PDNSPTOC1-operate DEFLPDEF1-operate EFHPTOC1-operate OR DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate ROVPTOV1-operate ROVPTOV3-operate ROVPTOV2-operate ARCSARC1-operate ARCSARC2-operate ARCSARC3-operate WPWDE1-operate WPWDE2-operate WPWDE3-operate PHLPTOC1-operate PHHPTOC1-operate PHHPTOC2-operate PHIPTOC1-operate DEFLPDEF1-operate EFHPTOC1-operate OR DEFLPDEF2-operate DEFHPDEF1-operate EFPADM1-operate EFPADM2-operate EFPADM3-operate INTRPTEF1-operate ROVPTOV1-operate ROVPTOV3-operate ROVPTOV2-operate OR TPGAPC2 IN1 OUT1 IN2 OUT2 WPWDE1-operate WPWDE2-operate WPWDE3-operate 21 A071346 V6 EN Figure 29: Alarm indication The signal outputs from the IED are connected to give dedicated information on: • Start of any protection function SO1 (X100:10-12) • Operation (trip) of any protection function SO2 (X100: 13-15) Section 3 1MRS756378 K REF615 standard configurations 66 REF615 Application Manual TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic timers (TPGAPC1..4) available in the IED. The remaining ones not described in the functional diagram are available in PCM600 for connection where applicable. 3.6 Standard configuration C 3.6.1 Applications The standard configuration for non-directional overcurrent and non-directional earthfault protection is mainly intended for cable and overhead-line feeder applications in directly or resistance earthed distribution networks. The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user flexibility for incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal functionality using PCM600. 3.6.2 Functions Table 21: Functions included in the standard | | | |