,否则任何其他站点都不能使用该地址。另一个缺点
如果不删除其他站中的接收DSP,则在
发送DSP或其通信接口已被移除。
将通信接口更换为另一个CI520通信接口,
见第4.6.5节,更换CI520。
删除发送的DSP后,请执行以下步骤以删除CI520
模块:
•重置CI520数据库元素上的IMPL终端。
•从CI520模块上拔下调制解调器电缆。
•卸下CI520模块。
其余通信接口将自动继续共享总线主设备
他们之间的责任,忽略被移除的站点。
3.2.1.4 CI520状态信息
自身通信接口CI520的状态信息可通过
DB元件Advant Fieldbus 100。
CI520的状态由Advant Fieldbus 100中的DIAG_I端子给出
DB元素。DIAG_I端子上给出了以下状态信息:
OK CI520正在运行。
IE CI520缺失或故障。
PE过程错误,例如电缆断裂。
ME CI520内部错误,请更换CI520。
SE System error(SE系统错误),例如,多个站点是时间主控站。
DC诊断已更改。
PSV CI520为无源。
DPL CI520只有默认参数。
I9-I15尚未定义interfaces will keep the CDPs in the scan tables and by this occupying bus bandwidth for no use.
As a sending CDP must be deleted from the station by which it is configured, the CDP signal
address can not be used by any other station unless the whole bus is restarted. Another drawback
of not removing receiving DSPs in other stations is that they will not be updated when the
sending DSP or its communication interface has been removed.
Replacing the communication interface with another CI520 communication interface,
see Section 4.6.5, Exchange of a CI520.
When the sending DSPs have been deleted, perform the following steps in removing the CI520
module:
• Reset the IMPL terminal on the CI520 data base element.
• Remove the modem cable from the CI520 module.
• Remove the CI520 module.
The remaining communication interfaces will automatically continue to share the bus master
responsibilities between them and ignore the removed station.
3.2.1.4 CI520 Status Information
The status information of the own communication interface, CI520, is available with the
DB element Advant Fieldbus 100.
The status of the CI520 is given by the DIAG_I terminal in the Advant Fieldbus 100
DB element. The following status information is given on the DIAG_I terminal:
OK CI520 is operating.
IE Missing or faulty CI520.
PE Process error, for example cable break.
ME CI520 internal error, replace CI520.
SE System error, for example several stations are time master.
DC Diagnostics has changed.
PSV The CI520 is passive.
DPL The CI520 only has default parameters.
I9 - I15 Not yet define